CyberPower OL3T030KERTHDS 3 phase HD Rack UPS 30KVA/30KW Charger
| Location | Availability |
|---|---|
Online (Delivery) | Preorder |
Notting Hill (Pickup) | Preorder |
Preston (Pickup) | Preorder |
West Melbourne (Pickup) | Preorder |
CyberPower OL3T030KERTHDS guarantees backup power and protection for IT equipment such as FTTx devices, networking devices and NAS/storage devices. It is typically integrated in the back office, server room, and data center environments. With integrated IGBT technology and intelligent DSP-based control, the product produces less input total harmonic distortion (THDi), achieving higher power efficiency. Supporting flexible placement, the selected product can be installed in a rack or tower configuration, and it's compatible with 19” standard rack cabinets. In addition, the product features parallel expansion, allowing the connections of multiple UPS units to reach higher capacity. Its color LCD with touch panel enables easy monitoring and configuration of the system. Furthermore, the LCD panel can also be adjusted to vertical or horizontal display through LCD setting.
Features
- Three-phase Design
- High Output Power Factor
- Color LCD Panel
- Generator Compatible
- UPS Parallel Expansion
- Smart Battery Management (SBM)
- PowerPanel Management Software
- Online (Double Conversion) UPS Topology
- Rack Modular Design
- LCD Touch Panel
- Pure Sine Wave Output
- Battery Cold Start
- SNMP/HTTP Remote Management Capability (Optional)
- Extended Battery Module (EBM)
General
| Three Phase |
| Tower |
| Online Double Conversion |
| ECO Mode Efficiency up to 98.9% |
| 95.8% |
| 95.5% |
| Yes |
| 4 |
Input
| Yes |
| Line to Neutral (L-N):220, 230, 240 Vac, Line to Line (L-L):380, 400, 415 Vac |
| Line to Neutral (L-N): 132 ~ 276 Vac |
| Line to Line (L-L): 228 ~ 478 Vac |
| 10% ~ -15% |
| 40 ~ 70 |
| ± 10 % |
| ± 20 % |
| 48.5 |
| <3% (Full Linear Load) |
| 0.99 |
| 125% Load for continuous operation, 150% Load for 10 min, 1000% Load for 5 ms |
| L1, L2, L3, N, G |
| Hardwire Terminal Block |
Output
| 30000 |
| 30000 |
| Pure Sine Wave |
| Configurable |
| Configurable |
| Line to Neutral (L-N):220, 230, 240 Vac, Line to Line (L-L):380, 400, 415 Vac |
| Balance Load: 1 % |
| 50 ± 0.2 |
| 60 ± 0.166 |
| 1 |
| ± 5 % |
| Internal Current Limiting, Fuse |
| 102~110% Load for 60 min, 110~125% Load for 10 min, 125~150% Load for 1 min, >150% Load for 200 ms |
| 102~110% Load for 60 min, 110~125% Load for 10 min, 125~150% Load for 1 min, >150% Load for 200 ms |
| 3 : 1 |
| THD<1% |
| THD<3% |
| Automatic Bypass |
| ± 4 |
| L1, L2, L3, N, G |
| Hardwire Terminal Block x 1 |
| 0 |
Battery
| 12 |
| 3.6 |
| VRLA |
| Configurable |
| ≤ 1 % |
| Yes |
| Yes |
| ±240 |
| BME480V55ART5U |
| Models rated 30kVA and above require at least two EBMs to support full capacity |
| SMBF17, SMBF20, SMBF26, SMBF33, SMBF40, SMBF65, BCA100N125, BCA12N63, BCA20N125, BCA40N125 |
| 12V x 40(Default)/32/36pcs |
Surge Protection & Filtering
| Yes |
Management & Communications
| Yes |
| Color LCD, LCD Touch Panel |
| Rotatable LCD – Manual |
| Operation Type, Power Status, Battery Status, Load Status, Fault & Warning, Other Information, Event & Log |
| Mode Setting, Input & Output, Battery Setting, Communication, Event & Log, Security Setting, Language |
| Yes |
| Alarm On/Off |
| RS485 x 1 + Dry Contact x 1 |
| Yes |
| Yes |
| Battery Mode, Low Battery, Overload, Overcharge, Overheat, UPS Fault, Replace Battery |
| PowerPanel Business (Recommended) |
| Yes - with optional RMCARD205 |
Physical
| Metal |
| Black |
| IP20 |
| Yes |
Physical Size - UPS Module
| 8.62 x 19.02 x 29.92 |
| 219 x 483 x 760 |
| 98.55 |
| 44.7 |
Environmental
| 32 ~ 104 |
| 0 ~ 40 |
| Derating to 80% load between 41℃ and 50℃ |
| 0 ~ 95 |
| 0-9,843 feet (0-3,000 meters) |
| At ≤1,000m above sea level, de-rate power by 1% per 100m between 1,000m and 3,048m |
| -40 ~ 158 |
| -40 ~ 70 |
| 0 ~ 95 |
| 66dBA(100% load) |
| 56dBA(50% load) |
Certifications
| CE, BSMI, IEC62040-1, IEC62040-2, CNS 14757-2, CNS 14843-1 |
| Yes |
| GTIN | 4711027798479 |
|---|